Page 162 - 2020DM-1210
P. 162
TH-P512 Modulating Output Thermostat
( 0~10vdc or 4~20mA )
Features:1. Analogic output control logic.
2. Input: 24 VAC nominal
3. Control signal output: Selectable by Jumper
1. 0~10VDC minimum 100 Ohm
2. 4~20 mA 100~500 Ohm
4. Off-Heat-Cool-Auto modes selec�on on pane
5. Temperature sampling rate: 4 seconds
6. Temperature indica�on sale: 0.1 °F
7. Single (2-pipe) & Dual (4-pipe) output models available
8. Cool / Heat operates logic:
Cool: Room temperature > Setpoint
Heat: Room temperature< Setpoint
9. Thermostat output shall turn to 100% when setpoint is
2 °F (1.1 °C) above or below setpoint.
10.Temperature display range: 32~99 °F (0~40 °C)
11.Temperature control range: 50~90 °F (10~32°C)
12.Dimension: 117 x 71 x 28 mm
13.Universal wiring back plate provided.
Model Available for choice
Output Fan speed Purge Auxiliary Setback Seasonal System
control heat Changeover switch
TH-P512-01 Dual None NO YES YES NO Off-Auto-
(4-pipe) Heat-Cool
TH-P512-02 Dual Off-Hi-Med-Lo YES YES YES NO Off-Auto-
(4-pipe) Heat-Cool
TH-P512-03 Dual Off-Hi-Med-Lo YES NO YES YES Off-Heat /
(2-pipe) Off-Cool
TH-P512-04 Dual None NO NO YES NO Off-Heat /
(2-pipe) Off-Cool
TH-P512-05 Dual None YES NO YES NO Off-Heat /
(2-pipe) Off-Cool
TH-P512-06 Dual Off-On YES YES YES NO Off-Auto-
(4-pipe) Heat-Cool
TH-P512-07 Dual Off-On YES NO YES NO Off-Heat /
(2-pipe) Off-Cool
TH-P512-08 Dual Off-On YES NO YES NO Off-Auto-
(4-pipe) Heat-Cool
TH-P512-09 Dual Off-Hi-Med-Lo YES YES YES YES Off-Auto-
(4-pipe) Heat-Cool
152